Description
These modules provide an isolated Profibus-DP network interface for up to six input channels. Differential inputs eliminate ground noise and each terminal block includes a cold junction compensation (CJC) sensor for more precise temperature measurements. Multi-range inputs accept signals from a variety of sensors and devices. High-resolution, low noise, A/D converters deliver high accuracy and reliability.
Input Ranges
Thermocouple (user-selectable type)
Type J, K, T, R, S, E, B, or N
DC Millivolts (user-selectable range)
±100mV or ±1V DC
Network Communication
Profibus-DP, RS-485 network up to 12Mbaud
Power Requirement
12 to 36V DC supply required
Approvals
Profibus PNO certified.
CE marked. UL, cUL listed.
Class I; Division 2; Groups A, B, C, D
Performance
Input
Configuration: Input ranges are selectable for a 3-channel group.
Accuracy:
Input Input Range Accuracy (typical)
Type J -210 to 760°C ±0.5°C
Type K -200 to 1372°C ±0.5°C
Type T -260 to 400°C ±0.5°C
Type R -50 to 1768°C ±1.0°C
Type S -50 to 1768°C ±1.0°C
Type E -200 to 1000°C ±0.5°C
Type B 260 to 1820°C ±1.0°C
Type N -230 to -170°C ±1.0°C
Type N -170 to 1300°C ±0.5°C
Voltage ±100mV or ±1V DC ±0.1% of span
Cold Junction Compensation (CJC) Accuracy: ±0.5°C
Thermocouple Break Detection: Upscale or downscale selection applies to all channels.
Analog to Digital Converter (A/D): 16-bit A/D converter
Noise Rejection:
Normal Mode: Better than 40dB @ 60Hz.
Common Mode: Better than 140dB @ 60Hz.
Input Filter Bandwidth: -3dB at 3Hz, typical
Environmental
Ambient Temperature:
Operating: -25 to 70°C (-13 to 158°F).
Storage: -40 to 85°C (-40 to 185°F)
Relative Humidity: 5 to 95%, non-condensing
Isolation:
1500V AC for 60 seconds or 250V AC continuous
3-way isolation between I/O, network, and power
The post 965PB: 4 or 6-Channel Input Profibus-DP Modules appeared first on Acromag.